Rs2k_Rider
DW's Resident Medic
I personally would get the 32A. I would also use one of these to add to circuit for pump
Outdoor / Garden Weatherproof Double Socket Waterproof | eBay UK
I dont see any reason for that to cause a problem. If the heater draws 27A then you will still be able to draw another 5A from the sockets. Plenty to run a pump and a radio I would think. Might be worth just checking rating of the pump tho to be safe
Incidently a more accurate calculation for the heater comes out at 26.08A m8.
so closer to 26amps than 27 lol
The pump only tells me this info - 220-240v~, 50Hz, 165W. I dont know how to convert that to Amps
So what would I do, run the armoured cable to the high amp 3 pin outlet.... then spur off that to a waterproof socket on the same feed ?